Alternator synchronization Image from Google images
The process of connecting an AC generator (alternator) to other AC generators is known as synchronization and is crucial for the generation of AC electrical power.
A DC generator can be connected to a power network by adjusting its open-circuit terminal voltage to match the network voltage by either adjusting its speed or its field excitation; the exact engine speed is not critical. However, an AC machine must match both the amplitude and the timing of the network voltage, which requires both speed and excitation to be systematically and closely controlled for synchronization. This extra complexity was one of the arguments against AC operation during the War of Currents in the 1880's. In modern systems, synchronization of generators is carried out by automatic systems.
Process
In the past, synchronization was performed manually using three-lamp method. Nowadays, the process is automatically operated and controlled with the aid of synchronization relays.
During installation of a generator, careful checks are made to ensure the generator terminals and all control wiring are correct so that the order of phases (phase sequence) matches the system. Connecting a generator with the wrong phase sequence will result in a short circuit as the system voltages are opposite to those of the generator terminal voltages.
The sequence of events is similar for manual or automatic synchronization. The generator is brought up to approximate synchronous speed by supplying more energy to its shaft, for example, opening the valves on a steam turbine, opening the gates on a hydraulic turbine, or increasing the fuel rack setting on a diesel engine. The field of the generator is energized and the voltage at the terminals of the generator is observed and compared with the system. The voltage magnitude must be the same as the system voltage.
Synchronizing lamps
Formerly, three light bulbs were connected between the generator terminals and the system terminals (or more generally, to the terminals of instrument transformers connected to generator and system). As the generator speed changes, the lights will rise and fall in intensity at a rate proportional to the difference between generator frequency and system frequency. When the voltage at the generator is opposite to the system voltage (either ahead or behind in phase), the lamps will be bright. When the voltage at the generator matches the system voltage, the lights will be dark. At that instant, the circuit breaker connecting the generator to the system may be closed and the generator will then stay in synchronism with the system.